Medium-voltage (MV) distribution networks, substations, renewable energy plants and industrial power systems all depend on mechanical connectors to join aluminium and copper conductors without a crimping tool.
The requirement is always the same: a low-resistance joint that stays stable through twenty years of thermal cycling, wind vibration and moisture exposure.
The Cembre MBS50-240E mechanical screw connector has been a reference product in this segment. It covers 50–240 mm² copper and aluminium conductors with stepless bolts and a tin-plated aluminium body, and it is qualified to CEI EN 61238-1-3.
For European utilities and EPC contractors, it is a familiar and well-documented choice.
The constraint is rarely performance — it is economics and availability.
A branded European connector carries a landed cost built from manufacturing, freight, multi-tier distribution and currency exposure, and a delivery cycle measured in weeks rather than days.
On a substation package with several thousand joints, that spread is visible in the bill of materials, and any customisation request — a different body length, a customer logo, a special packing configuration — moves the item from stock to a special order.
Jera Line manufactures the CCBVzT-36-4.S(H)-70-240 stepless shear bolt mechanical connector for exactly this application. It covers 70–240 mm², carries the same IEC 61238-1-3 qualification, and is produced in a factory that builds the moulds, runs the assembly lines and tests the batches in-house.
One point of accuracy before the comparison.
The Cembre MBS50-240E mechanical splice starts at 50 mm².
The Jera Line CCBVzT-36-4.S(H)-70-240 stepless shear bolt mechanical connector starts at 70 mm², so it is a direct replacement across the 70–240 mm² range, not across the full 50–240 mm² range.
Projects specifying 50–70 mm² conductors should confirm the smaller Jera Line size before ordering.
The comparison below covers only the range the two products genuinely share.
The Cembre MBS50-240E is a mechanical splice that joins or extends two insulated power conductors by bolted pressure rather than compression.
Its stepless bolts carry no preset break-off point: each bolt is tightened to an optimal torque, with an anti-friction washer under the head keeping friction low so the contact force builds up without damaging the conductor strands.
One body covers the full 50–240 mm² range, so a single reference replaces what would otherwise be three or four separate items.
The Jera Line CCBVzT-36-4.S(H)-70-240 stepless shear bolt mechanical connector follows the same installation logic.
Two stepless shear-head bolts sit on a tin-plated aluminium alloy body; the conductor is inserted, the bolts are driven with a standard hex key, and the joint is complete. No hydraulic press, no crimping die, no torque calibration sheet.
That last point matters on site. A conventional compression joint requires the correct die, the correct tool and an operator who follows the compression sequence exactly.
A mechanical connector removes all three variables. The bolt either reaches its shear point or it does not — the installation result is visible without a gauge.
The installation sequence, in four steps.
Clean the conductor with a wire brush and solvent, insert it fully into the body until it seats against the end stop, drive the two shear-head bolts alternately with a hex key so the contact force builds evenly, and stop when both heads break away.
The whole operation takes a few minutes per joint and needs no press, no die set and no torque calibration sheet — which is why bolted connectors dominate repair work and confined joint bays.
| Item | Specification |
|---|---|
| Product code | CCBVzT-36-4.S(H)-70-240 |
| Conductor range | 70–240 mm² |
| Conductor material | Copper / Aluminium |
| Rated voltage | up to 36 kV |
| Bolt configuration | 2 stepless shear-head bolts |
| Body material | Tin-plated aluminium alloy |
| Bolt material | Brass |
| Installation | Standard hex key, no crimping tool |
| Qualification | IEC 61238-1-3 |
Drop-in replacement, checked item by item.
Purchasing engineers compare four things before approving an alternative: conductor range, installation method, body material and qualification.
Across the shared 70–240 mm² window, the two products align on all four — identical range, both installed with a hex key and no press, both built on a tin-plated aluminium body for bimetallic Cu/Al service, and both qualified to the IEC 61238-1-3 family.
Two differences are worth stating plainly rather than glossing over. First, voltage: the Cembre MBS series is published up to 52 kV at system level, while the Jera Line item is rated to 36 kV — so it suits systems up to 36 kV and should not be substituted above that.
Second, bolt behaviour: the Cembre design relies on tightening to an optimal torque with an anti-friction washer under each bolt, whereas the Jera Line design uses a shear head that breaks away at the calibrated value, giving a visual confirmation that the joint is complete.
Both approaches reach a controlled contact force; they simply verify it differently. Note also that the two manufacturers use the word stepless in slightly different senses — Cembre applies it to the absence of a preset break-off point, while Jera Line applies it to the thread travelling the full conductor range, combined with a shear head that confirms completion.
Read the datasheet, not the adjective.
What one reference is worth in the warehouse.
A distributor supporting 70, 95, 120, 150, 185 and 240 mm² joints would otherwise stock a ladder of connector sizes, each with its own safety stock level and its own risk of going obsolete.
Collapsing that ladder into a single stepless reference cuts the stock value, the shelf space and the picking error rate, and it lets a crew carry one box on the truck instead of six.
Raw material is inspected before production, and each batch of CCBVzT-36-4.S(H)-70-240 stepless shear bolt mechanical connectors is strictly tested in-house before shipment.
Routine checks cover contact resistance, bolt torque verification and dimensional inspection, so electrical and mechanical performance stays consistent from lot to lot.
1. One Reference Covers 70–240 mm² Without Spacers
The stepless thread uses its full travel for any conductor in the range, so a warehouse does not need to stock four sizes and a crew does not need to select an insert before installing.
For a contractor running joints across 95, 150, 185 and 240 mm² in the same project, that single reference removes both a stocking decision and a wrong-part risk on site.
2. Shear-Head Completion Without a Torque Gauge
The bolt head separates at the calibrated torque, so the installer knows the joint is finished by looking at it.
No torque wrench reading, no second check by a supervisor, no disputed installation record.
On a night shift or in a confined joint bay, that is a real reduction in rework.
3. Bimetallic Stability on Copper and Aluminium
A tin-plated aluminium alloy body with brass bolts forms a barrier between copper and aluminium conductors, limiting galvanic corrosion at the transition. The same connector serves an aluminium feeder and a copper equipment tail, which is the normal mix in retrofitted substations.
4. Rated for 36 kV MV Service
The connector is built for medium-voltage cable joints, terminations and switchgear connections up to 36 kV, with the dielectric clearance and body geometry that MV accessory assembly requires — not a repurposed LV part.
5. IEC 61238-1-3 Qualification, Verified In-House
Heat-cycle and short-circuit performance is evaluated to the IEC 61238-1-3 requirements for MV connectors, with resistance measurements and torque verification repeated in Jera Line's own laboratory.
Test documentation is available for tender submission.
1. Underground MV Distribution Cable Joints
The standard use case: joining 70–240 mm² aluminium or copper XLPE cables in ring-main and radial distribution circuits, whether in a straight joint, a transition joint or a repair splice.
2. Substations, Switchgear and Transformer Connections
Inside a substation, space is tight and conductor transitions between aluminium busbar and copper equipment tails are routine. A mechanical connector removes the need to bring a press and a die set into a live-adjacent compartment.
3. Renewable Energy Collector Circuits
Wind and solar plants run long MV collector lines with many series joints. A single connector reference covering 70–240 mm² simplifies the material list, and batch-level test records support the quality dossier that lenders increasingly request.
4. Industrial MV Installations
Process plants, data centres and heavy manufacturing sites connect MV feeders to distribution transformers and switchgear. The mechanical joint is the practical choice where a press cannot be positioned or where cable tails are short.
5. Overhead-to-Underground Transitions and Emergency Repair
Where an overhead MV line drops into cable, or where a faulted joint must be restored quickly, a bolted connector needs only a hex key and a cleaned conductor — no tooling logistics, no waiting for a press to arrive.
For MV projects specified between 70 and 240 mm² and operating at up to 36 kV, the Jera Line CCBVzT-36-4.S(H)-70-240 stepless shear bolt mechanical connector is a direct alternative to the Cembre MBS50-240E Mechanical Screw Connector.
It matches the shared conductor range, the no-crimp hex-key installation, the tin-plated aluminium body and the IEC 61238-1-3 qualification, and it adds shear-head completion that confirms the joint visually.
The honest boundaries are two: it does not cover the 50–70 mm² segment, and it is rated to 36 kV rather than the 52 kV published for the Cembre MBS series. Where a project falls inside those limits, the case for switching is straightforward — factory-direct pricing, a delivery cycle in days, batch-level test records and OEM support on workable minimums.
If you are evaluating a Cembre MBS50-240E alternative mechanical connector for an upcoming MV package, send the conductor sizes and system voltage to the Jera Line team.
We will confirm the correct reference, supply free samples for a trial joint, and provide the test documentation your tender requires.